The Allen-Bradley PowerFlex 525 reports problems as F-codes on its display. This page is the plain-English version of the common ones: what each code means, what usually causes it in the field, and where to look first. Type in the box to filter the table.

Safety first: drives hold lethal DC bus charge after power-off and can restart machinery when a fault clears. Lockout/tagout, wait the manufacturer's specified discharge time before touching terminals, and have qualified personnel do electrical work. This reference is a quick-orientation aid — always confirm against the official manual for your exact model and firmware.

No rows match your search.

CodeNameWhat it meansWhat to check first
F002Auxiliary InputAn external device wired to the auxiliary input opened the circuitCheck the external interlock/device wired to the aux input and its wiring
F003Power LossIncoming line power dipped or a phase dropped while runningCheck supply voltage, upstream fuses/breaker, and incoming connections
F004UnderVoltageDC bus voltage fell below the minimum limitLow line voltage or brownout — monitor supply; check for sagging feeds under load
F005OverVoltageDC bus voltage exceeded the maximum limitOften regen from a fast-decelerating load — extend decel time or add a brake resistor; check for line transients
F006Motor StalledMotor could not accelerate — drive hit current limit too longMechanical jam or overload; too-short accel time; undersized drive for the load
F007Motor OverloadElectronic overload (I²t) tripped for the motorVerify motor OL current parameter matches the nameplate; check for mechanical overload
F008Heatsink OvrTempDrive heatsink exceeded temperature limitClean the heatsink/fan, check enclosure ventilation and ambient temperature, verify fan operation
F012HW OverCurrentInstantaneous output current exceeded the hardware trip levelShort circuit or ground fault in motor cable/motor; sudden load slam — inspect cable and motor insulation
F013Ground FaultCurrent leakage path to ground detected on the outputMegger the motor and cable; check for moisture in the motor junction box
F015Load LossOutput torque fell below the configured load-loss levelBroken belt/coupling or lost load — inspect the mechanical transmission
F021Output Ph LossOne output phase to the motor was lostCheck motor leads and connections at drive and motor terminal box
F029Analog In LossThe analog speed-reference signal was lostBroken 4-20 mA/0-10 V wiring or failed transmitter — check the reference source and cable
F033Auto Rstrt TriesThe drive exhausted its configured automatic restart attemptsFind and fix the underlying recurring fault; the restart counter is telling you it keeps happening
F038Phase U to GndGround fault detected on output phase UInsulation test motor and cable on that phase; check terminations
F039Phase V to GndGround fault detected on output phase VAs F038, phase V
F040Phase W to GndGround fault detected on output phase WAs F038, phase W
F041Phase UV ShortShort circuit detected between output phases U and VInspect motor cable and motor windings; do not keep resetting into a short
F042Phase UW ShortShort circuit between phases U and WAs F041
F043Phase VW ShortShort circuit between phases V and WAs F041
F048Params DefaultedThe drive was commanded to reset parameters to defaultsExpected after a reset — reload or re-enter your application parameters
F059Safety OpenThe Safe Torque Off (STO) safety inputs are openCheck the safety circuit (relay, e-stop chain, jumpers if STO unused) wired to the safety terminals
F063SW OverCurrentOutput current exceeded the software trip levelCheck for mechanical overload, aggressive accel, or incorrect motor data
F064Drive OverloadDrive I²t overload — running above rating too longLoad exceeds drive rating — check sizing, duty cycle, and cooling
F070Power UnitFault detected in the drive power sectionCycle power; if it persists the power stage has likely failed — drive service/replacement
F071Net LossCommunication loss on the embedded EtherNet/IP networkCheck network cabling, switch, and the controller connection; review comm loss action settings
F081Comm LossCommunication loss on the DSI/serial portCheck serial/keypad wiring and the connected device
F094Function LossThe function-loss input openedCheck the device wired to the function-loss terminal
F100Parameter ChksumDrive memory checksum error in stored parametersReset to defaults (P041) and reprogram; if recurring, the control board memory is suspect
F111Safety HardwareFault in the safety (STO) input hardwareCheck safety wiring for miswire/overvoltage; persistent fault means control board service
F114uC FailureThe drive microcontroller detected an internal failureCycle power; persistent F114 is an internal hardware fault — contact Rockwell support/replace the drive

Plain-language summaries based on Rockwell Automation's PowerFlex 520-series user manual (publication 520-UM001) and common field practice. Confirm details for your firmware in the official manual before acting.

How to clear a PowerFlex 525 fault

  1. Read the code first (and note it) — clearing without reading throws away the diagnosis. Recent faults are stored in the drive's fault buffer (viewable via display group parameters or software).
  2. Fix the cause — most faults on this list return immediately if the underlying condition remains.
  3. Clear it — press the red Stop/reset key, cycle a digital input configured for fault reset, send a comms reset from the PLC, or cycle power. If the drive restarts automatically, treat that behavior with respect: auto-restart on a machine that can move people or product must be a deliberate, risk-assessed choice.

The three fault families worth recognizing

New to drives? Start with what a VFD is and how it works — the fault list makes far more sense once the rectifier/DC-bus/inverter architecture is clear. Setting one up? See the PowerFlex 525 parameters guide.

Frequently asked questions

What does F059 mean on a PowerFlex 525?

F059 "Safety Open" means the Safe Torque Off (STO) safety inputs are open — the drive is being held safe by its safety circuit. Check the e-stop chain, safety relay, or (if STO is unused) the safety-terminal jumpers per the manual.

How do I clear a fault on a PowerFlex 525?

Fix the cause first, then reset: press the red Stop key, pulse a digital input configured for fault reset, send a reset over the network from the PLC, or cycle power. Faults whose cause remains will return immediately.

What causes F005 OverVoltage on a PowerFlex 525?

Usually regeneration: a high-inertia load decelerating too fast pumps energy back into the DC bus. Lengthen decel time (P040) or add a dynamic-brake resistor; also rule out line transients.

Where is the official PowerFlex 525 fault list?

Rockwell Automation publication 520-UM001 (PowerFlex 520-Series Adjustable Frequency AC Drive User Manual), available free from Rockwell\u2019s literature library — always the final authority for your firmware revision.