Yaskawa V1000 Fault Codes: The Plain-English Reference

By Industrial Automation Pro · Published 2026-07-31 · 7 min read

The Yaskawa V1000 compact drive reports faults as short letter codes on its LED operator — oC, oV, Uv1 and family. This searchable table is the plain-English decoder: meaning, usual field cause, and where to start.

Safety first: drives hold lethal DC bus charge after power-off and can restart machinery when a fault clears. Lockout/tagout, wait the manufacturer's specified discharge time before touching terminals, and have qualified personnel do electrical work. This reference is a quick-orientation aid — always confirm against the official manual for your exact model and firmware.

No rows match your search.

CodeNameWhat it meansWhat to check first
oCOvercurrentOutput current exceeded the instantaneous trip levelShort/ground fault in motor or cable; sudden load slam; accel too aggressive — inspect before repeated resets
oVOvervoltageDC bus voltage exceeded the limitRegenerative load on decel — extend decel time or add braking; check supply for transients
Uv1UndervoltageDC bus voltage fell below the limitLine sag/brownout or lost phase — check supply and input wiring
oH / oH1Heatsink OverheatDrive temperature exceeded the alarm/trip levelClean heatsink, verify fan, check enclosure cooling and ambient
oL1Motor OverloadElectronic motor thermal overload trippedVerify motor rated current setting matches nameplate; find the mechanical overload
oL2Drive OverloadDrive thermal overload — output above rating too longCheck drive sizing vs the real load and duty cycle
oL3Overtorque 1Output current exceeded the configured overtorque detection levelInvestigate the mechanical load — jam, binding, or process change
GFGround FaultGround leakage current detected on the outputInsulation-test the motor and cable; look for moisture ingress
SCShort Circuit / IGBTOutput short-circuit or power-transistor fault detectedInspect motor and cable for shorts; persistent SC with motor disconnected = drive power stage
LFOutput Phase LossAn output phase to the motor was lostCheck motor lead connections at both ends
PFInput Phase LossExcessive DC bus ripple — an input phase is missing/imbalancedCheck incoming three-phase supply, fuses, and terminals
EF0-EF8External FaultAn external fault input (terminal S1-S8 or comms) is activeThe number tells you which terminal — check the device wired to it
CEComm Error (Modbus)MEMOBUS/Modbus communication was lostCheck RS-485 wiring, termination, addresses, and the master
bUSOption Comm ErrorCommunication lost on the option-card networkCheck option card seating and network health
oPrOperator DisconnectThe keypad/operator was disconnected while the drive was set to require itReseat the operator or change the run-source configuration
CoFCurrent OffsetCurrent-detection offset drifted out of rangeCycle power; persistent CoF suggests drive hardware service
FbLPID Feedback LossThe PID feedback signal fell below the loss-detection levelCheck the transmitter and its wiring (classic 4-20 mA break symptom)
SToSafe Torque OffThe safe-disable inputs are openCheck the safety circuit wired to the safe-disable terminals; jumpers per manual if STO is unused
ErrEEPROM Write ErrorParameter memory write failedRetry; persistent Err means control board memory trouble

Plain-language summaries based on Yaskawa's V1000 technical manual and field practice. The same code family appears across Yaskawa's A1000/P1000 drives with model-specific details — dedicated pages for those are coming. Confirm against the official manual for your model.

Clearing faults on a V1000

Fix the cause, then reset: press RESET/Stop on the operator, toggle a digital input configured for fault reset, reset over Modbus from the controller, or cycle power. The drive stores a fault history in its monitor parameters — read it before clearing; a pattern across the history (five Uv1 events overnight, say) is a diagnosis in itself.

Reading Yaskawa's code language

Drive fundamentals live in our VFD guide; the Allen-Bradley equivalent table is at PowerFlex 525 fault codes.

Frequently asked questions

What does oC mean on a Yaskawa V1000?

Overcurrent: the output current spiked past the instantaneous trip level. Usual suspects are a short or ground fault in the motor cable or motor, a mechanical slam load, or too-aggressive acceleration — inspect before resetting repeatedly.

What does Uv1 mean on a Yaskawa drive?

Main-circuit undervoltage: the DC bus dropped below its limit, almost always from supply sag, a brownout, or a lost input phase. Check incoming power and connections.

How do I reset a fault on a V1000?

Remove the cause, then press RESET on the operator, toggle a reset-configured digital input, reset via Modbus, or cycle power. Check the fault history in the monitor parameters first — patterns are diagnoses.