HomeFault Codes & Parameter References › Siemens VFD Fault Codes

Siemens VFD Fault Codes: MICROMASTER & SINAMICS Explained

By Industrial Automation Pro · Published 2026-07-31 · 8 min read

"Siemens VFD fault codes" actually means two different code systems, because two drive generations are everywhere in the field: the legacy MICROMASTER family (F00xx codes) and the current SINAMICS family (five-digit codes like F30001, plus A-prefixed alarms). This page decodes the common members of both.

Safety first: drives hold lethal DC bus charge after power-off and can restart machinery when a fault clears. Lockout/tagout, wait the manufacturer's specified discharge time before touching terminals, and have qualified personnel do electrical work. This reference is a quick-orientation aid — always confirm against the official manual for your exact model and firmware.

MICROMASTER 420/430/440 — F00xx codes

No rows match your search.

CodeNameWhat it meansWhat to check first
F0001OvercurrentOutput current exceeded the trip thresholdShort/ground fault in cable or motor; accel too fast; motor data wrong
F0002OvervoltageDC bus voltage exceeded the limitRegen on decel — lengthen ramp-down or add braking; check line
F0003UndervoltageDC bus fell below the limitSupply dip or phase loss — check the incoming line
F0004Inverter OvertempDrive heatsink over temperatureFan, dust, enclosure ventilation, ambient
F0005Inverter I²tDrive thermal overload from sustained excess loadCheck drive sizing vs actual duty
F0011Motor OvertempMotor thermal model (or sensor) trippedVerify motor data parameters; find the overload; check motor cooling
F0041Motor Data ID FailAutomatic motor-data identification failedCheck motor wiring and nameplate entries; motor must be appropriate size for the drive
F0070CB Setpoint FaultSetpoint lost from the communication boardCheck fieldbus wiring/master; review telegram configuration
F0072USS Setpoint FaultSetpoint lost on the USS serial linkCheck the serial link and master polling
F0085External FaultA digital input configured as external fault is activeCheck the device wired to that input

SINAMICS (G120 family and relatives) — F3xxxx codes

No rows match your search.

CodeNameWhat it meansWhat to check first
F30001OvercurrentOutput current exceeded the trip thresholdCable/motor short, ground fault, wrong motor data, aggressive ramps
F30002OvervoltageDC link voltage exceeded the limitDecel too fast for the inertia — extend ramp or add braking
F30003UndervoltageDC link below limitLine sag/phase loss — verify supply
F30004Converter OvertempPower-unit heatsink over temperatureCooling path: fan, fins, enclosure, ambient
F30005I²t OverloadPower unit thermally overloaded by sustained loadDrive sizing vs real duty cycle
F30021Ground FaultGround fault detected on the outputInsulation-test motor and cable

Plain-language summaries based on Siemens' MICROMASTER and SINAMICS documentation and field practice. SINAMICS fault lists are long and model-specific — confirm your exact code in the List Manual for your drive and firmware.

Faults vs alarms on SINAMICS

SINAMICS distinguishes F (fault) — the drive trips and must be acknowledged — from A (alarm) — a warning that displays while the drive keeps running. An A-code is the drive giving you time to act before the matching F-code stops the line; treat recurring alarms as scheduled maintenance telling you its own date.

Acknowledging faults

After fixing the cause: acknowledge from the operator panel (BOP/IOP), a digital input configured for acknowledge, the fieldbus (PROFINET/PROFIBUS telegram bit), or a power cycle. Both families keep a fault history — on recurring problems, the history plus a timestamp pattern is worth more than any single code.

The universal drive-fault logic

Notice how Siemens' list rhymes with Rockwell's and Yaskawa's: overcurrent, over/undervoltage, overtemperature, overload, ground fault, comm loss. Every VFD is the same rectifier → DC bus → inverter machine, so every VFD fails in the same six ways — learn the physics once and every brand's fault list becomes readable.

Frequently asked questions

What is the difference between F and A codes on Siemens drives?

F codes are faults — the drive trips and must be acknowledged after the cause is fixed. A codes are alarms — warnings shown while the drive keeps running, often the early form of a coming fault.

What does F0002 / F30002 mean on a Siemens drive?

DC-link overvoltage in both families — classically caused by decelerating a high-inertia load too quickly, which regenerates energy into the bus. Extend the ramp-down time or add braking capacity.

Where do I find the full Siemens fault list for my drive?

In the List Manual for your exact model and firmware (each SINAMICS family has one, free on Siemens\u2019 support portal). Fault lists are model-specific — this page covers the common shared codes.

Planning a project in this area?

Tell us what you are automating and where you are stuck — we will point you in the right direction.

Get In Touch